T088, T087, Terminal block group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 89

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

89

Programming and Parameters

Chapter 3

Terminal Block Group (continued)

t087 [EM Brk On Delay]

Related Parameter(s):

P045

Sets the time the drive remains at minimum frequency (after releasing the brake coil relay) before stopping if EM Brake Control Mode is enabled with

P045

[Stop Mode].

Values

Default:

2.00 s

Min/Max:

0.00/10.00 s

Display:

0.01 s

Frequency

Time

[Minimum Freq]

[EM Brk Off Delay]

[EM Brk On Delay]

Stop

commanded

Start

commanded

EM Brk

de-energized (On)

Drive stops

EM Brk

energized (Off)

Ramp accel

Ramp decel

t088 [Analog Out Sel]

Related Parameter(s):

t090

PowerFlex 525 only.

The 0-10V, 0-20 mA or 4-2 0 mA analog output can be used to provide a signal proportional to several drive conditions. This parameter also selects which analog calibration parameters
to use.

Values

Default:

0

Min/Max:

0/23

Display:

1

PF 525

Options

Output Range

Minimum Output Value

Maximum Output Value =

t089

[Analog Out High]

Filter

(1)

(1) Filter A is a single pole digital filter with a 162 ms time constant. Given a 0...100% step input from a steady state, the output of Filter A takes 500 ms to get to 95% of maximum, 810 ms to get to 99%,

and 910 ms to get to 100%.

Related
Parameter

0 “OutFreq 0-10”

0-10V

0V = 0 Hz

[Maximum Freq]

None

b001

1 “OutCurr 0-10”

0-10V

0V = 0 A

200% Drive Rated Current

Filter A

b003

2 “OutVolt 0-10”

0-10V

0V = 0 V

120% Drive Rated Output Volts

None

b004

3 “OutPowr 0-10”

0-10V

0V = 0 kW

200% Drive Rated Power

Filter A

b017

4 “OutTorq 0-10”

0-10V

0V = 0 A

200% Drive Rated Current

Filter A

d382

5 “TstData 0-10”

0-10V

0V = 0000

65535 (Hex FFFF)

None

6 “Setpnt 0-10”

0-10V

0V = 0%

100.0% Setpoint setting

None

t090

7 “DCVolt 0-10”

0-10V

0V = 0V

100.0% of trip value

None

b005

8 “OutFreq 0-20”

0-20 mA

0 mA = 0 Hz

[Maximum Freq]

None

b001

9 “OutCurr 0-20”

0-20 mA

0 mA = 0 A

200% Drive Rated Current

Filter A

b003

10 “OutVolt 0-20”

0-20 mA

0 mA = 0 V

120% Drive Rated Output Volts

None

b004

11 “OutPowr 0-20”

0-20 mA

0 mA = 0 kW

200% Drive Rated Power

Filter A

b017

12 “OutTorq 0-20”

0-20 mA

0 mA = 0 A

200% Drive Rated Current

Filter A

d382

13 “TstData 0-20”

0-20 mA

0 mA = 0000

65535 (Hex FFFF)

None

14 “Setpnt 0-20”

0-20 mA

0 mA = 0%

100.0% Setpoint setting

None

t090

15 “DCVolt 0-20”

0-20 mA

0 mA = 0V

100.0% of trip value

None

b005

16 “OutFreq 4-20”

4-20 mA

4 mA = 0 Hz

[Maximum Freq]

None

b001

17 “OutCurr 4-20”

4-20 mA

4 mA = 0 A

200% Drive Rated Current

Filter A

b003

18 “OutVolt 4-20”

4-20 mA

4 mA = 0 V

120% Drive Rated Output Volts

None

b004

19 “OutPowr 4-20”

4-20 mA

4 mA = 0 kW

200% Drive Rated Power

Filter A

b017

20 “OutTorq 4-20”

4-20 mA

4 mA = 0 A

200% Drive Rated Current

Filter A

d382

21 “TstData 4-20”

4-20 mA

4 mA = 0000

65535 (Hex FFFF)

None

22 “Setpnt 4-20”

4-20 mA

4 mA = 0%

100.0% Setpoint setting

None

t090

23 “DCVolt 4-20”

4-20 mA

4 mA = 0V

100.0% of trip value

None

b005

Advertising