Rockwell Automation Publication 520-UM001G-EN-E - September 2014

15

Chapter

1

Installation/Wiring

This chapter provides information on mounting and wiring the PowerFlex 520-
series drives.

Most start-up difficulties are the result of incorrect wiring. Every precaution must
be taken to assure that the wiring is done as instructed. All items must be read and
understood before the actual installation begins.

Mounting Considerations

Mount the drive upright on a flat, vertical and level surface.

Protect the cooling fan by avoiding dust or metallic particles.

For information on...

See page...

Mounting Considerations

15

AC Supply Source Considerations

19

General Grounding Requirements

20

Fuses and Circuit Breakers

22

Power and Control Module

27

Control Module Cover

30

Power Module Terminal Guard

30

Power Wiring

31

Power Terminal Block

34

Common Bus/Precharge Notes

35

I/O Wiring

35

Control I/O Terminal Block

36

Start and Speed Reference Control

46

CE Conformity

49

ATTENTION: The following information is merely a guide for proper
installation. Rockwell Automation cannot assume responsibility for the
compliance or the noncompliance to any code, national, local or otherwise for
the proper installation of this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if codes are ignored during
installation.

Frame

Screw Size

Screw Torque

A

M5 (#10...24)

1.56...1.96 Nm (14...17 lb-in.)

B

M5 (#10...24)

1.56...1.96 Nm (14...17 lb-in.)

C

M5 (#10...24)

1.56...1.96 Nm (14...17 lb-in.)

D

M5 (#10...24)

2.45...2.94 Nm (22...26 lb-in.)

E

M8 (5/16 in.)

6.0...7.4 Nm (53...65 lb-in.)