06

DigIn TermBlk 06 Preset Freq

Program with t066 [DigIn TermBlk 06].
Current consumption is 6 mA.

t066

07

DigIn TermBlk 07/
Pulse In

Start Source 2
+ Speed
Reference2

Program with t067 [DigIn TermBlk 07]. Also functions as a Pulse
Train input for reference or speed feedback. The maximum
frequency is 100 kHz. Current consumption is 6 mA.

t067

08

DigIn TermBlk 08 Jog Forward

Program with t068 [DigIn TermBlk 08].
Current consumption is 6 mA.

t068

C1

C1

This terminal is tied to the RJ-45 port shield. Tie this terminal to
a clean ground in order to improve noise immunity when using
external communication peripherals.

C2

C2

This is the signal common for the communication signals.

S1

Safety 1

Safety input 1. Current consumption is 6 mA.

S2

Safety 2

Safety input 2. Current consumption is 6 mA.

S+ Safety +24V

+24V supply for safety circuit. Internally tied to the +24V DC
source (Pin 11).

11

+24V DC

Referenced to Digital Common.
Drive supplied power for digital inputs.
Maximum output current is 100 mA.

12

+10V DC

Referenced to Analog Common.
Drive supplied power for 0...10V external potentiometer.
Maximum output current is 15 mA.

P047

,

P049

13

±10V In

Not Active

For external 0-10V (unipolar) or ±10V (bipolar) input supply or
potentiometer wiper.
Input impedance:

Voltage source = 100 k

Allowable potentiometer resistance range = 1...10 k

P047

,

P049

,

t062

,

t063

,

t065

,

t066

,

t093

,

A459

,

A471

14

Analog Common

Return for the analog I/O. Electrically isolated (along with the
analog I/O) from the rest of the drive.

15

4-20mA In

Not Active

For external 4-20 mA input supply.
Input impedance = 250

P047

,

P049

,

t062

,

t063

,

t065

,

t066

,

A459

,

A471

16

Analog Output

OutFreq 0-10

The default analog output is 0-10V. To convert a current value,
change the Analog Output jumper to 0-20 mA. Program with
t088 [Analog Out Sel]. Maximum analog value can be scaled
with t089 [Analog Out High].
Maximum Load: 4-20 mA = 525

Ω (10.5V)

0-10V = 1 k

Ω (10 mA)

t088

,

t089

17

Opto Output 1

Motor Running Program with t069 [Opto Out1 Sel].

Each Opto-Output is rated 30V DC 50 mA (Non-inductive).

t069

,

t070

,

t075

18

Opto Output 2

At Frequency

Program with t072 [Opto Out1 Sel].
Each Opto-Output is rated 30V DC 50 mA (Non-inductive).

t072

,

t073

,

t075

19

Opto Common

The emitters of the Optocoupler Outputs (1 and 2) are tied
together at Optocoupler Common. Electrically isolated from the
rest of the drive.

(1) See Footnote (1) on

page 37

.