A442, A443, Advanced program group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 111: Important

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

111

Programming and Parameters

Chapter 3

Advanced Program Group (continued)

A440 [PWM Frequency]

Related Parameter(s):

A540

Sets the carrier frequency for the PWM output waveform. The chart below provides derating guidelines based on the PWM frequency setting.

Values

Default:

4.0 kHz

Min/Max:

2.0/16.0 kHz

Display:

0.1 kHz

% Output Curent (A)

68

84

88

80
76

96

100

92

72

64
60
56
50

Carrier Frequency (kHz)

8

7

6

5

4

3

2

1

15

14

16

13

12

11

10

9

IMPORTANT

Ignoring derating guidelines can cause reduced drive performance. The drive may automatically reduce the PWM carrier frequency at low output speeds,
unless prevented from doing so by A540 [Var PWM Disable].

A441 [Droop Hertz@ FLA]

PowerFlex 525 only.

Reduces the frequency based on current. This frequency is subtracted from the commanded output frequency. Generally Slip and Droop would not both be used, but if both are enabled
they simply subtract from each other. Typically used in load sharing schemes.

Values

Default:

0.0 Hz

Min/Max:

0.0/10.0 Hz

Display:

0.1 Hz

PF 525

A442 [Accel Time 2]

Related Parameter(s):

P044

Time for the drive to ramp from 0.0 Hz to

P044

[Maximum Freq] if Accel Time 2 is selected.

Accel Rate = [Maximum Freq] / [Accel Time]

Values

Default:

10.00 s

Min/Max:

0.00/600.00 s

Display:

0.01 s

Speed

0

Time

[Maximum Freq]

[Accel Time x]

[Decel Time x]

0

Acceleration

Deceleration

A443 [Decel Time 2]

Related Parameter(s):

P044

Time for the drive to ramp from

P044

[Maximum Freq] to 0.0 Hz if Decel Time 2 is selected.

Decel Rate = [Maximum Freq] / [Decel Time]

Values

Default:

10.00 s

Min/Max:

0.00/600.00 s

Display:

0.01 s