Advanced Program Group (continued)

A546 [FlyStrt CurLimit]

Used to determine when the drive has matched the motor frequency if flying start is enabled.

Values

Default:

150%

Min/Max:

30/200%

Display:

1%

A547 [Compensation]

Enables/disables correction options that may improve problems with motor instability.

Options

0 “Disabled”

No compensation.

1 “Electrical” (Default)

Some drive/motor combinations have inherent instabilities which are exhibited as non-sinusodial motor currents.
This setting attempts to correct this condition

2 “Mechanical”

Some motor/load combinations have mechanical resonances which can be excited by the drive current regulator.
This setting slows down the current regulator response and attempts to correct this condition.

3 “Both”

A548 [Power Loss Mode]

Sets the reaction to a loss of input power.

Options

0 “Coast” (Default)

Drive faults and motor coasts to a stop.

1 “Decel”

Drive decelerates and attempts to keep the DC bus voltage above the undervoltage level.

A549 [Half Bus Enable]

Enables/disables the power ride through function which allows the drive to maintain power to the motor at 50% drive input voltage during short-term power sag conditions.

Options

0 “Disabled” (Default)

1 “Enabled”

ATTENTION: To guard against drive damage, a minimum line impedance must be provided to limit inrush current when the power line recovers. The input
impedance should be equal or greater than the equivalent of a 5% transformer with a VA rating 6 times the drive's input VA rating if Half Bus is enabled.

A550 [Bus Reg Enable]

Enables/disables the bus regulator.

Options

0 “Disabled”

1 “Enabled” (Default)

A551 [Fault Clear]

Stop drive before changing this parameter.

Resets a fault and clears the fault queue.

Options

0 “Ready/Idle” (Default)

1 “Reset Fault”

Resets the active fault but does not clear any fault buffer.

2 “Clear Buffer”

Resets the active fault and clears all fault buffers to “0”.

A552 [Program Lock]

Related Parameter(s):

A553

Protects parameters against change by unauthorized personnel with a 4-digit password.

Values

Default:

0000

Min/Max:

0000/9999

Display:

1111