P046 [Start Source 1]

Related Parameter(s):

b012

,

t064

,

C125

P048 [Start Source 2]
P050 [Start Source 3]

Stop drive before changing this parameter.

Configures the start source of the drive. Changes to these inputs take effect as soon as they are entered. P046 [Start Source 1] is the factory default start source unless overridden.
See

Start and Speed Reference Control on page 46

for more information.

Options

1 “Keypad”

[Start Source 1] default

2 “DigIn TrmBlk”

[Start Source 2] default

3 “Serial/DSI”

[Start Source 3] default for PowerFlex 523

4 “Network Opt”

(1)

5 “EtherNet/IP”

(2)

[Start Source 3] default for PowerFlex 525

(1) Select this setting if using the optional PowerFlex 25-COMM-E2P, 25-COMM-D, or 25-COMM-P adapters as the start source.
(2) Setting is specific to PowerFlex 525 drives only.

IMPORTANT

For all settings except when t064 [2-Wire Mode] is set to 1 “Level Sense”, the drive must receive a leading edge from the start input for the drive to start after a
stop input, loss of power, or fault condition.

P047 [Speed Reference1]

Related Parameter(s):

C125

P049 [Speed Reference2]
P051 [Speed Reference3]

Selects the source of speed command for the drive. Changes to these inputs take effect as soon as they are entered. P047 [Speed Reference1] is the factory default speed reference
unless overridden.
See

Start and Speed Reference Control on page 46

for more information.

Options

1 “Drive Pot”

[Speed Reference1] default

2 “Keypad Freq”

3 “Serial/DSI”

[Speed Reference3] default for PowerFlex 523

4 “Network Opt”

(1)

5 “0-10V Input”

[Speed Reference2] default

6 “4-20mA Input”

7 “Preset Freq”

8 “Anlg In Mult”

(2)

9 “MOP”

10 “Pulse Input”

11 “PID1 Output”

12 “PID2 Output”

(2)

13 “Step Logic”

(2)

14 “Encoder”

(2)

15 “EtherNet/IP”

(2)

[Speed Reference3] default for PowerFlex 525

16 “Positioning”

(2)

Referencing from

A558

[Positioning Mode]

(1) Select this setting if using the optional PowerFlex 25-COMM-E2P, 25-COMM-D, or 25-COMM-P adapters as the speed reference.
(2) Setting is specific to PowerFlex 525 drives only.

P052 [Average kWh Cost]

Related Parameter(s):

b025

Sets the average cost per kWh.

Values

Default:

0.00

Min/Max:

0.00/655.35

Display:

0.01