Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 1

Installation/Wiring

Maximum motor cable length must not exceed the maximum length
indicated in

PowerFlex 520-Series RF Emission Compliance and

Installation Requirements on page 52

for compliance with radio frequency

emission limits for the specific standard and installation environment.

Connections and Grounding

(1) Some installations require a shielded enclosure. Keep wire length as short as possible between the enclosure entry point and the

EMI filter.

Additional Installation Requirements

This section provides information on additional requirements for Class C1 and
C2 installation, such as enclosures and EMC cores.

PowerFlex 520-Series RF Emission Compliance and Installation Requirements

Filter Type

Standard/Limits

EN61800-3 Category C1
EN61000-6-3
CISPR11 Group 1 Class B

EN61800-3 Category C2
EN61000-6-4
CISPR11 Group 1 Class A
(Input power ≤ 20 kVA)

EN61800-3 Category C3
(I ≤ 100 A)
CISPR11 Group 1 Class A
(Input power > 20 kVA)

Internal

10 m (33 ft)

20 m (66 ft)

External

(1)

(1) See

Appendix B

for more information on optional external filters.

30 m (16 ft)

100 m (328 ft)

100 m (328 ft)

IMPORTANT

EMC cores are included with:

drives that have an internal EMC filter (25x-xxxxN114)
external EMC filter accessory kit (25-RFxxx)

IMPORTANT

An enclosure, shielded input cable, and EMC cores are not required to meet
class C3 requirements.

R/L1
S/L2
T/L3

U/T1
V/T2

W/T3

EMI fittings and metal conduit

IP 30/NEMA 1/UL Type 1
option kit or EMC kit

Shielded enclosure(1)

Building structure steel

Enclosure ground connection

EMI filter

L1'
L2'
L3'

L1
L2
L3

Shielded motor cable