Rockwell Automation Publication 520-UM001G-EN-E - September 2014

191

RS485 (DSI) Protocol

Appendix C

Supported Modbus Function
Codes

The peripheral interface (DSI) used on PowerFlex 520-series drives supports
some of the Modbus function codes.

Writing (06) Logic Command
Data

The PowerFlex 520-series drive can be controlled through the network by
sending Function Code 06 writes to register address 2000H (Logic Command).

P046

[Start Source 1] must be set to 3 “Serial/DSI” in order to accept the

commands. PowerFlex 523 drives support only Velocity bit definitions.
PowerFlex 525 drives can use Parameter

C122

[Cmd Stat Select] to select either

Velocity or Position bit definitions.

Supported Modbus Function Codes

Modbus Function Code (Decimal)

Command

03

Read Holding Registers

06

Preset (Write) Single Register

16 (10 Hexadecimal)

Preset (Write) Multiple Registers

IMPORTANT

Modbus devices can be 0-based (registers are numbered starting at 0) or 1-
based (registers are numbered starting at 1). Depending on the Modbus
Master used, the register addresses listed on the following pages may need to
be offset by +1. For example, Logic Command may be register address 8192 for
some master devices (e.g. ProSoft 3150-MCM SLC Modbus scanner) and 8193
for others (e.g. PanelViews).

TIP

Powerup/Reset the drive after selecting an option for C122 [Cmd Stat Select]
for the change to take effect.