Advanced program group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 119

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

119

Programming and Parameters

Chapter 3

Advanced Program Group (continued)

A510 [Freq 1]
A512 [Freq 2]
A514 [Freq 3]

PowerFlex 525 only.

Sets the “Vector” control mode frequency.

Values

Default:
Freq 1:
Freq 2:
Freq 3:

8.33%
15.00%
20.00%

Min/Max:

0.00/200.00%

Display:

0.01%

PF 525

A511 [Freq 1 BW]
A513 [Freq 2 BW]
A515 [Freq 3 BW]

PowerFlex 525 only.

Speed control loop bandwidth for “Vector” control mode.

Values

Default:

10 Hz

Min/Max:

0/40 Hz

Display:

1 Hz

PF 525

A521 [Freq 1 Kp]

Related Parameter(s):

A509

,

A510

A523 [Freq 2 Kp]
A525 [Freq 3 Kp]

PowerFlex 525 only.

Sets P-gain of “Vector” control mode when in frequency region 1, 2 or 3 for faster speed response during dynamic-state where motor is still accelerating. If

A509

[Speed Reg Sel] is set

to 1 “Manual”, these parameters can be changed.

Values

Default:

100.0%

Min/Max:

0.0/500.0%

Display:

0.1%

PF 525

A522 [Freq 1 Ki]

Related Parameter(s):

A509

,

A510

A524 [Freq 2 Ki]
A526 [Freq 3 Ki]

PowerFlex 525 only.

Sets I-gain of “Vector” control mode when in frequency region 1, 2 or 3 for faster speed response during steady-state where motor is at its rated speed. If

A509

[Speed Reg Sel] is set to

1 “Manual”, these parameters can be changed.

Values

Default:

0.100 s

Min/Max:

0.000/10.000 s

Display:

0.001 s

PF 525