Appendix G

Safe-Torque-Off Function

Example 3 – Safe-Torque-Off Connection with Coast-to-Stop Action
Using External +24V supply, SIL 3/PL e

Stop Category 0 – Coast

(1) Enclosure Recommended. External wiring failure modes must be considered as described in EN ISO 13849-2. Enclosure or other

measure to exclude these failure modes should be used.

Circuit Status

Circuit shown with guard door closed and system ready for normal drive
operation.

Operating Principle

This is a dual channel system with monitoring of the Safe-Torque-Off circuit and
drive. Opening the guard door will switch the input circuits (S11-S12 & S21-
S22) to the Minotaur monitoring safety relay unit. The output circuits (13-14 &
23-24 & 33-34) will cause the output contact and Safe-Torque-Off Enable circuit
to trip and the motor will coast to stop. To restart the drive, the Minotaur safety
relay must first be reset followed by a valid start command to the drive.

Fault Detection

A single fault detected on the Minotaur safety input circuits will result in the
lock-out of the system at the next operation and will not cause loss of the safety
function.

Closed

Open

External +24V DC

24V DC COM

MSR127TP

Reset

+24V DC

PF 525

Stop

Start

COM

Gate control

power supply

Gate control

circuit

AC line

input power

S1

S2

X1 AUX

X2

A1 Coil

A2

External

contactor

100-C

100S-C

13 23 33

14 24 34

M

A1 S11 S52 S12 13 23 33 41

S21 S22 S34 A2 14 24 34 42

(1)