B010, Basic display group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 72

Advertising
background image

72

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 3

Programming and Parameters

Basic Display Group (continued)

b007 [Fault 1 Code]

Related Parameter(s):

F604

-

F610

b008 [Fault 2 Code]
b009 [Fault 3 Code]

A code that represents a drive fault. Codes appear in these parameters in the order they occur (

b007

[Fault 1 Code] = the most recent fault). Repetitive faults are only recorded once.

See

Fault and Diagnostic Group

for more information.

Values

Default:

Read Only

Min/Max:

F0/F127

Display:

F0

b010 [Process Display]

Related Parameter(s):

b001

,

A481

,

A482

32 bit parameter.

Output frequency scaled by [Process Disp Hi] and [Process Disp Lo].

Values

Default:

Read Only

Min/Max:

0/9999

Display:

1

32

b012 [Control Source]

Related Parameter(s):

P046

,

P047

,

P048

,

P049

,

P050

,

P051

,

t062

,

t063

,

t065

-

t068

,

L180

-

L187

,

A410

-

A425

Active source of the Start Command and Frequency Command. Normally defined by the settings of

P046

,

P048

,

P050

[Start Source x] and

P047

,

P049

,

P051

[Speed Referencex].

See

Start and Speed Reference Control on page 46

for more information.

Values

Default:

Read Only

Min/Max:

0000/2165

Display:

0000

Start Command Source

Digit 1

1 = Keypad
2 = DigIn TrmBlk (Parameters

t062

,

t063

,

t065

-

t068

)

3 = Serial/DSI
4 = Network Opt

(1)

5 = EtherNet/IP

(2)

(1)

Select this setting if using the optional PowerFlex 25-COMM-E2P, 25-COMM-D, or
25-COMM-P adapters as the Start source and/or Frequency source.

(2)

Setting is specific to PowerFlex 525 drives only.

Frequency Command Source

Digit 2 & 3

00 = Other
01 = Drive Pot
02 = Keypad
03 = Serial/DSI
04 = Network Opt

(1)

05 = 0-10V Input
06 = 4-20mA Input
07 = Preset Freq (Parameters

A410

-

A425

)

08 = Anlg In Mult

(2)

09 = MOP
10 = Pulse Input
11 = PID1 Output
12 = PID2 Output

(2)

13 = Step Logic (Parameters

L180

-

L187

)

(1)

14 = Encoder

(2)

15 = EtherNet/IP

(2)

16 = Positioning

(2)

Frequency Command Source

Digit 4

0 = Other (Digit 2 & 3 are used. Digit 4 is not shown.)
1 = Jog
2 = Purge

Not Used

Display reads...

Description

2004

Start source comes from Network Opt and Frequency source is Purge.

113

Start source comes from Serial/DSI and Frequency source comes from PID1 Output.

155

Start source and Frequency source comes from EtherNet/IP.

052

Start source comes from DigIn TrmBlk and Frequency source from 0-10V Input.

011

Start source comes from Keypad and Frequency source comes from Drive Pot.

Example

Advertising
This manual is related to the following products: