Advanced program group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 113

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

113

Programming and Parameters

Chapter 3

Advanced Program Group (continued)

A456 [PID 1 Trim Hi]

A468 [PID 2 Trim Hi]

PowerFlex 525 only.

Scales the upper value of the trim frequency when trim is active.

Values

Default:

60.0 Hz

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz

PF 525

A457 [PID 1 Trim Lo]

A469 [PID 2 Trim Lo]

PowerFlex 525 only.

Scales the lower value of the trim frequency when trim is active.

Values

Default:

0.0 Hz

Min/Max:

0.0/500.0 Hz

Display:

0.1 Hz

PF 525

A458 [PID 1 Trim Sel]

A470 [PID 2 Trim Sel]

PowerFlex 525 only.

Stop drive before changing this parameter.

Sets the PID output as trim to the source reference.

Options

0 “Disabled” (Default)

PID Trim is disabled.

1 “TrimOn Pot”

2 “TrimOn Keypd”

3 “TrimOn DSI”

4 “TrimOn NetOp”

5 “TrimOn 0-10V”

6 “TrimOn 4-20”

7 “TrimOn Prset”

8 “TrimOn AnMlt”

(1)

9 “TrimOn MOP”

10 “TrimOn Pulse”

11 “TrimOn Slgic”

(1)

12 “TrimOn Encdr”

(1)

13 “TrimOn ENet”

(1)

(1) Setting is specific to PowerFlex 525 drives only.

PF 525

Advertising
This manual is related to the following products: