t070 [Opto Out1 Level]

Related Parameter(s):

t069

,

t072

t073 [Opto Out2 Level]

32 bit parameter.

PowerFlex 525 only.

Determines the on/off point for the digital outputs when

t069

or

t072

[Opto Outx Sel] is set to the values shown below.

Values

Default:

0

Min/Max:

0/9999

Display:

1

32

PF 525

Min/Max Value Range Based On [Opto Outx Sel] Setting

6:

0...500 Hz

10: 0...100%

16: 0.1...9999 s

20: 0/1

7:

0...180%

11 0/1

17: 1...9999 counts 26: 0...150%

8:

0...815V

13 0...800

18: 0...180

°

t075 [Opto Out Logic]

PowerFlex 525 only.

Determines the logic (Normally Open/NO or Normally Closed/NC) of the digital outputs only.

Values

Default:

0

Min/Max:

0/3

Display:

1

PF 525

Setting Digital Out 1 Logic Digital Out 2 Logic

0

NO

NO

1

NC

NO

2

NO

NC

3

NC

NC