A562 [Find Home Freq]

PowerFlex 525 only.

Sets the maximum frequency the drive uses when “Find Home” is issued.

Values

Default:

10.0 Hz

Min/Max:

0.1/500.0 Hz

Display:

0.1 Hz

PF 525

A563 [Find Home Dir]

Stop drive before changing this parameter.

PowerFlex 525 only.

Sets the direction the drive commands when “Find Home” is issued.

Options

0 “Forward” (Default)

1 “Reverse”

PF 525

A564 [Encoder Pos Tol]

PowerFlex 525 only.

Sets the “At Position” and the “At Home’ tolerance around the encoder count. The value is added to and subtracted from the target encoder unit value to create the tolerance range.

Values

Default:

100

Min/Max:

1/50000

Display:

1

PF 525

A565 [Pos Reg Filter]

PowerFlex 525 only.

Sets the error signal filter in the position regulator.

Values

Default:

8

Min/Max:

0/15

Display:

1

PF 525

A566 [Pos Reg Gain]

PowerFlex 525 only.

Sets the gain adjustment for the position regulator.

Values

Default:

3.0

Min/Max:

0.0/200.0

Display:

0.1

PF 525