RS485 (DSI) Protocol

Velocity Bit Definitions

Comm Logic Command – C122 = 0 “Velocity”

Address (Decimal)

Bit(s)

Description

2000H (8192)

0

1 = Stop, 0 = Not Stop

1

1 = Start, 0 = Not Start

2

1 = Jog, 0 = No Jog

3

1 = Clear Faults, 0 = Not Clear Faults

5, 4

00 = No Command

01 = Forward Command

10 = Reverse Command

11 = No Command

6

1 = Force Keypad Control, 0 = Not Force Keypad Control

7

1 = MOP Increment, 0 = Not Increment

9, 8

00 = No Command

01 = Accel Rate 1 Enable

10 = Accel Rate 2 Enable

11 = Hold Accel Rate Selected

11, 10

00 = No Command

01 = Decel Rate 1 Enable

10 = Decel Rate 2 Enable

11 = Hold Decel Rate Selected

14, 13, 12

000 = No Command

001 = Freq. Source = P047 [Speed Reference1]

010 = Freq. Source = P049 [Speed Reference2]

011 = Freq. Source = P051 [Speed Reference3]

100 = A410 [Preset Freq 0]

101 = A411 [Preset Freq 1]

110 = A412 [Preset Freq 2]

111 = A413 [Preset Freq 3]

15

1 = MOP Decrement, 0 = Not Decrement