F081

DSI Comm Loss

2

Communications between the drive and
the Modbus or DSI master device have
been interrupted.

Cycle power.
Check communications cabling.
Check Modbus or DSI setting.
Check Modbus or DSI status.
Modify using

C125

[Comm Loss

Action].

Connecting I/O terminals C1 and C2

to ground may improve noise
immunity.

Replace wiring, Modbus master

device, or control module.

F082

Opt Comm Loss

2

Communications between the drive and
the network option card have been
interrupted.

Cycle power.
Reinstall option card in drive.
Modify using

C125

[Comm Loss

Action].

Replace wiring, port expander,

option card, or control module.

F083

(1)

EN Comm Loss

2

Internal communications between the
drive and the embedded EtherNet/IP
adapter have been interrupted.

Cycle power.
Check EtherNet/IP setting.
Check drive’s Ethernet settings and

diagnostic parameters.

Modify using

C125

[Comm Loss

Action].

Replace wiring, Ethernet switch, or

control module.

F091

(1)

Encoder Loss

2

Requires differential encoder.
One of the 2 encoder channel signals is
missing.

Check Wiring.
If

P047

,

P049

,

P051

[Speed

Referencex] = 16 “Positioning” and

A535

[Motor Fdbk Type] = 5 “Quad

Check”, swap the Encoder channel
inputs or swap any two motor leads.

Replace encoder.

F094

Function Loss

2

“Freeze-Fire” (Function Loss) input is
inactive, input to the programmed
terminal is open.

Close input to the terminal and cycle
power.

F100

Parameter Chksum 2

Drive parameter non-volatile storage is
corrupted.

Set

P053

[Reset To Defalts] to 2 “Factory

Rset”.

F101

External Storage

2

External non-volatile storage has failed. Set

P053

[Reset To Defalts] to 2 “Factory

Rset”.

F105

C Connect Err

2

Control module was disconnected while
drive was powered.

Clear fault and verify all parameter
settings. Do not remove or install the
control module while power is applied.

F106

Incompat C-P

2

The PowerFlex 525 control module does
not support power modules with 0.25
HP power rating.

Change to a different power module.
Change to a PowerFlex 523 control

module.

F107

Replaced C-P

2

The control module could not recognize
the power module. Hardware failure.

Change to a different power module.
Replace control module if changing

power module does not work.

F109

Mismatch C-P

2

The control module was mounted to a
different drive type power module.

Set

P053

[Reset To Defalts] to 3 “Power

Reset”.

F110

Keypad Membrane 2

Keypad membrane failure /
disconnected.

Cycle power.
Replace control module if fault

cannot be cleared.

F111

(1)

Safety Hardware

2

Safety input enable hardware
malfunction. One of the safety inputs is
not enabled.

Check safety input signals. If not

using safety, verify and tighten
jumper for I/O terminals S1, S2 and
S+.

Replace control module if fault

cannot be cleared.

F114

uC Failure

2

Microprocessor failure.

Cycle power.
Replace control module if fault

cannot be cleared.