Drive does not power up – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 153

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

153

Troubleshooting

Chapter 4

Drive does not power up.

Motor is rotating at zero Hz or slip frequency is not correct.

Cause(s)

Indication

Corrective Action

No input power to drive.

None

Check the power circuit.
Check the supply voltage.
Check all fuses and disconnects.

Control module is not connected properly to power module.

None

1. Remove power.
2. Verify that the control module is properly and fully installed on the power module.
3. Reapply power.

Cause(s)

Indication

Corrective Action

Incorrect speed calculation.

Improper speed.

Verify

P032

[Motor NP Hertz].

Reduce boost with

A530

[Boost Select].

Set

P036

[Motor NP RPM] to motor synchronous speed.