Rs485 (dsi) protocol, Network wiring, Appendix c – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 189: Appendix

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

189

Appendix

C

RS485 (DSI) Protocol

PowerFlex 520-series drives support the RS485 (DSI) protocol to allow efficient
operation with Rockwell Automation peripherals. In addition, some Modbus
functions are supported to allow simple networking. PowerFlex 520-series drives
can be multi-dropped on an RS485 network using Modbus protocol in RTU
mode.

PowerFlex 520-Series Drive Network

For information regarding EtherNet/IP or other communication protocols, refer
to the appropriate user manual.

Network Wiring

Network wiring consists of a shielded 2-conductor cable that is daisy-chained
from node to node.

Network Wiring Diagram Example

Controller

Esc

Sel

Esc

Sel

Esc

Sel

Esc

Sel

ATTENTION: Never attempt to connect a Power over Ethernet (PoE) cable to the
RS485 port. Doing so may damage the circuitry.

IMPORTANT

The shield is connected at ONLY ONE end of each cable segment.

C1 C2

Master

4

5

TxRxD-

TxRxD+

TxRxD-

TxRxD+

TxRxD-

TxRxD+

Shield

Shield

Shield

120 ohm resistor

120 ohm resistor

X

X

X

FRONT

PIN 8

PIN 1

TxRxD-

TxRxD+

RS485

(DSI)

AK-U0-RJ45-TB2P

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

DC- DC+

C1 C2

TxRxD-

TxRxD+

RS485

(DSI)

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

DC- DC+

PowerFlex 525

Node 1

4

5

PowerFlex 523

Node 2

4

5

PowerFlex 525

Node “n”

Advertising