90

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 3

Programming and Parameters

Terminal Block Group (continued)

t089 [Analog Out High]

PowerFlex 525 only.

Scales the maximum output value (V or mA) when the source setting is at maximum.

Values

Default:

100%

Min/Max:

0/800%

Display:

1%

PF 525

t090 [Anlg Out Setpt]

Related Parameter(s):

t088

PowerFlex 525 only.

Sets the percentage of output desired when

t088

[Analog Out Sel] is set to 6, 14 or 22 “Analog Setpoint”.

Values

Default:

0.0%

Min/Max:

0.0/100.0%

Display:

0.1%

PF 525

t091 [Anlg In 0-10V Lo]

Related Parameter(s):

P043

,

t092

,

t093

Stop drive before changing this parameter.

Sets the percentage (based on 10V) of input voltage applied to the 0-10V analog input used to represent

P043

[Minimum Freq].

Analog inversion can be accomplished by setting this value larger than

t092

[Anlg In 0-10V Hi].

If

t093

[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, this parameter is ignored.

Values

Default:

0.0%

Min/Max:

0.0/200.0%

Display:

0.1%

t092 [Anlg In 0-10V Hi]

Related Parameter(s):

P044

,

t091

,

t093

Stop drive before changing this parameter.

Sets the percentage (based on 10V) of input voltage applied to the 0-10V analog input used to represent

P044

[Maximum Freq].

Analog inversion can be accomplished by setting this value smaller than

t091

[Anlg In 0-10V Lo].

If

t093

[10V Bipolar Enbl] is set to 1 “Bi-Polar In”, the same value applies to positive and negative voltage.

Values

Default:

100.0%

Min/Max:

0.0/200.0%

Display:

0.1%

t093 [10V Bipolar Enbl]

Related Parameter(s):

t091

,

t092

PowerFlex 525 only.

Enables/disables bi-polar control. In bi-polar mode direction is commanded by the polarity of the voltage.
If bi-polar control is enabled,

P043

[Minimum Freq] and

t091

[Anlg In 0-10V Lo] are ignored.

Options

0 “Uni-Polar In” (Default)

0-10V only

1 “Bi-Polar In”

±10V

PF 525