Chapter 3

Programming and Parameters

Options

48 “2-Wire FWD”

(only for DigIn TermBlk 02)

[DigIn TermBlk 02] default. Select 2-Wire FWD for this input.
Select this option and set

P046

,

P048

or

P050

[Start Source x] to 2 “DigIn TrmBlk” to configure [Start Source x] to a 2-wire run

forward mode. Also see

t064

[2-Wire Mode] for level trigger settings.

49 “3-Wire Start”

(only for DigIn TermBlk 02)

Select 3-Wire Start for this input.
Select this option and set

P046

,

P048

or

P050

[Start Source x] to 2 “DigIn TrmBlk” to configure [Start Source x] to a 3-wire start

mode.

50 “2-Wire REV”

(only for DigIn TermBlk 03)

[DigIn TermBlk 03] default. Select 2-Wire REV for this input.
Select this option and set

P046

,

P048

or

P050

[Start Source x] to 2 “DigIn TrmBlk” to configure [Start Source x] to a 2-wire run

reverse mode. Also see

t064

[2-Wire Mode] for level trigger settings.

For PowerFlex 523 drives, this setting will be disabled If [DigIn TermBlk 03] is set to 7 “Preset Freq”.

51 “3-Wire Dir”

(only for DigIn TermBlk 03)

Select 3-Wire Dir for this input.
Select this option and set

P046

,

P048

or

P050

[Start Source x] to 2 “DigIn TrmBlk” to change the direction of [Start Source x].

For PowerFlex 523 drives, this setting will be disabled If [DigIn TermBlk 03] is set to 7 “Preset Freq”.

52 “Pulse Train”

(PF523: only for DigIn TermBlk 05)
(PF525: only for DigIn TermBlk 07)

Select pulse train for this input.
Use

P047

,

P049

and

P051

[Speed Referencex] to select pulse input.

Jumper for DigIn TermBlk 05 or 07 Sel must be moved to Pulse In.

(1) This function may be tied to one input only.
(2) Setting is specific to PowerFlex 525 drives only.

t064 [2-Wire Mode]

Related Parameter(s):

P045

,

P046

,

P048

,

P050

,

t062

,

t063

Stop drive before changing this parameter.

Programs the mode of trigger only for

t062

[DigIn TermBlk 02] and

t063

[DigIn TermBlk 03] when 2-wire option is being selected as

P046

,

P048

or

P050

[Start Source x].

Options

0 “Edge Trigger” (Default)

Standard 2-Wire operation.

1 “Level Sense”

I/O Terminal 01 “Stop” = Coast to stop. Drive will restart after a Stop command when:

Stop is removed

and

Start is held active

I/O Terminal 03 “Run REV”

2 “Hi-Spd Edge”

Outputs are kept in a ready-to-run state. The drive will respond to a Start command within 10 ms.

I/O Terminal 01 “Stop” = Coast to stop.

I/O Terminal 03 “Run REV”

3 “Momentary”

Drive will start after a momentary input from either the Run FWD input (I/O Terminal 02) or the Run REV input (I/O Terminal

03).

I/O Terminal 01 “Stop” = Stop according to the value set in

P045

[Stop Mode].

ATTENTION: Hazard of injury exists due to unintended operation. When t064 [2-Wire Mode] is set to
option 1, and the Run input is maintained, the Run inputs do not need to be toggled after a Stop input for
the drive to run again. A Stop function is provided only when the Stop input is active (open).

IMPORTANT

There is greater potential voltage on the output terminals when using this option.