Unstable response on – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 221

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

221

PID Set Up

Appendix F

2.

Adjust the integral gain (leave the proportional gain set as in Step 1). After
a step change in the PID Feedback:

If the response is too slow (see

Slow Response – Over Damped on

page 221

), or the PID Feedback does not become equal to the PID

Reference, decrease A462 or A474 [PID x Integ Time].

If there is a lot of oscillation in the PID Feedback before settling out
(see

Oscillation – Under Damped on page 221

), increase A462 or

A474 [PID x Integ Time].

3.

At this point, the differential gain may not be needed. However, if after
determining the values for A461 or A473 [PID x Prop Gain] and A462 or
A474 [PID x Integ Time]:

Response is still slow after a step change, increase A463 or A475 [PID x
Diff Rate].

Response is still unstable, decrease A463 or A475 [PID x Diff Rate].

The following figures show some typical responses of the PID loop at different
points during adjustment of the PID Gains.

Unstable Response

Slow Response – Over Damped

Oscillation – Under Damped

PID Feedback

PID Reference

Time

PID Feedback

PID Reference

Time

PID Feedback

PID Reference

Time

Advertising
This manual is related to the following products: