Smart start-up with basic program group parameters, Smart – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 61

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

61

Start Up

Chapter 2

Smart Start-Up with Basic
Program Group Parameters

The PowerFlex 520-series drive is designed so that start up is simple and efficient.
The Basic Program Group contains the most commonly used parameters. See

Programming and Parameters on page 65

for detailed descriptions of the

parameters listed here, as well as the full list of available parameters.

Polish

(1)

Y

Turkish

(1)

Y

Czech

(1)

Y

(1) Due to a limitation of the LCD Display, some of the characters for Polish, Turkish, and Czech will be modified.

Language

Keypad/LCD Display

RSLogix 5000/
Logix Designer

Connected Components
Workbench

= Stop drive before changing this parameter.
= Parameter is specific to PowerFlex 525 drives only.

No.

Parameter

Min/Max

Display/Options

Default

P030

[Language]

1/15

1 = English
2 = Français
3 = Español
4 = Italiano
5 = Deutsch
6 = Reserved
7 = Português
8 = Reserved
9 = Reserved
10 = Reserved
11 = Reserved
12 = Polish
13 = Reserved
14 = Turkish
15 = Czech

1

Selects the language displayed.
Important: The setting takes effect after the drive
is power cycled.

P031

[Motor NP Volts]

10V (for 200V Drives), 20V
(for 400V Drives), 25V (for
600V Drives)/Drive Rated
Volts

1V

Based on Drive Rating

Sets the motor nameplate rated volts.

P032

[Motor NP Hertz]

15/500 Hz

1 Hz

60 Hz

Sets the motor nameplate rated frequency.

P033

[Motor OL Current]

0.0/(Drive Rated Amps x 2)

0.1 A

Based on Drive Rating

Sets the motor nameplate overload current.

P034

[Motor NP FLA]

0.0/(Drive Rated Amps x 2)

0.1 A

Drive Rated Amps

Sets the motor nameplate FLA.

P035

[Motor NP Poles]

2/40

1

4

Sets the number of poles in the motor.

P036

[Motor NP RPM]

0/24000 rpm

1 rpm

1750 rpm

Sets the rated nameplate rpm of motor.

P037

[Motor NP Power]

0.00/Drive Rated Power

0.01 kW

Drive Rated Power

Sets the motor nameplate power. Used in PM
regulator.

P038

[Voltage Class]

2/3

2 = “480V”
3 = “600V”

3

Sets the voltage class of 600V drives. Only applicable
to 600V drives.

P039

[Torque Perf Mode]

0/3

0 = “V/Hz”
1 = “SVC”
2 = “Economize”
3 = “Vector”

(1)

1

Selects the motor control mode.

(1) Setting is specific to PowerFlex 525 drives only.

PF 525

PF 525

Advertising