Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 208

Advertising
background image

208

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Appendix E

Encoder/Pulse Train Usage and Position StepLogic Application

L190

...

L197

[Stp Logic Time x] are the parameters that define the time the drive

will remain in each corresponding step if that step is time-based. For example, if

L192

[Stp Logic Time 2] is set to 5.0 seconds and that step is time-based, the

drive will remain in Step 2 for 5.0 seconds. Note that this is the total time in that
step, not the time at that position. Therefore, it will include the time needed to
accelerate, run, and decelerate to that position.

L180

...

L187

[Stp Logic x] are the parameters that allow additional flexibility and

control various aspects of each step when a positioning mode is selected that
utilizes the Step Logic functions. Note that in Positioning mode these parameters
have a different function than when used for normal velocity Step Logic. Each of
the 4 digits controls one aspect of the each position step. The following is a listing
of the available settings for each digit:

A415

[Preset Freq 5]

L185

[Stp Logic 5]

L210

[Step Units 5]

A416

[Preset Freq 6]

L186

[Stp Logic 6]

L212

[Step Units 6]

A417

[Preset Freq 7]

L187

[Stp Logic 7]

L214

[Step Units 7]

IMPORTANT

The default value for

A410

[Preset Freq 0] is 0.00 Hz. This value needs to be

changed or the drive will not be able to move during Step 0.

Frequency Source

Step Source

Position Source

Advertising
This manual is related to the following products: