Chapter 1

Installation/Wiring

3 Wire SNK Control -
Non-Reversing

Internal Supply (SNK)

3 Wire SRC Control -
Reversing
P046 [Start Source 1] = 2,
t062 [DigIn TermBlk 02]
= 49 and t063 [DigIn
TermBlk 03] = 51
A momentary input will
start the drive. A stop
input to I/O Terminal 01
will stop the drive as
specified by

P045

[Stop

Mode]. I/O Terminal 03
determines direction.

Internal Supply (SRC)

External Supply (SRC)

Each digital input draws 6 mA.

3 Wire SNK Control -
Reversing

Internal Supply (SNK)

Opto Output (1 & 2)

(1)

t069

[Opto Out1 Sel]

determines Opto-Output 1
(I/O Terminal 17)
operation.

t072

[Opto Out2 Sel]

determines Opto-Output 2
(I/O Terminal 18)
operation.
When using Opto-Output
with an inductive load
such as a relay, install a
recovery diode parallel to
the relay as shown, to
prevent damage to the
output.

Opto-Output 1

Each Opto-Output is rated 30V DC 50 mA (Non-inductive).

Analog Output

(1)

t088

[Analog Out Sel]

determines analog output
type and drive conditions.
0-10V,
1k

Ω minimum

0-20 mA/4-20 mA,
525

Ω maximum

t088

[Analog Out Sel] = 0 through 23

The Analog Output Select jumper must be set to match the analog output signal mode set in

t088

[Analog Out Sel].

(1) Feature is specific to PowerFlex 525 drives only.

I/O

Connection Example

Stop

Start

01
02

04

11

01
02
03

Stop

Start

Direction

+24V

Common

Stop

Start

Direction

01
02
03
04

Stop

Start

Direction

01
02
03
04

Common

+24V

CR

19

17

14

16

Common

+