Fault and Diagnostic Group (continued)

F661 [Status @ Fault 1]
F663 [Status @ Fault 3]
F665 [Status @ Fault 5]

F662 [Status @ Fault 2]

Related Parameter(s):

b006

F664 [Status @ Fault 4]

F666 [Status @ Fault 6]
F668 [Status @ Fault 8]
F670 [Status @ Fault10]

PowerFlex 525 only.

F667 [Status @ Fault 7]
F669 [Status @ Fault 9]

Displays the value of

b006

[Drive Status] with the most recent 10 faults occurred.

[Status@ Fault 1] stores the most recent fault, [Status@ Fault 2] stores the second most recent fault and [Status@ Fault 3] stores the third most recent fault.

Values

Default:

Read Only

Min/Max:

0/0x1F

Display:

1

PF 525

1 = Condition True, 0 = Condition False

Running

Digit 1

Forward

Digit 2

Accelerating

Digit 3

Decelerating

Digit 4

SafetyActive

(1)

Digit 5

(1)

Setting is specific to PowerFlex 525 drives only.

F681 [Comm Sts - DSI]

Displays the status of the RS485 serial (DSI) port to the drive.

Values

Default:

Read Only

Min/Max:

0000/1911

Display:

0000

1 = Condition True, 0 = Condition False

Rx

Digit 1

Tx

Digit 2

Status

Digit 3

Error

Digit 4

Not Used

Digit 3 (Connection Status)

0

“Not Active”

1

“Modbus slave network (external Modbus master)”

2

“Modbus multi-drive w/ internal com option master”

3

“Modbus multi-drive w/ embedded com master”

(1)

(1)

Setting is specific to PowerFlex 525 drives only.

4

“DSI peripheral connected”

5...8 “Reserved”

9

“RS-485 network faulted”

F682 [Comm Sts - Opt]

Displays the status of the internal communication to the drive.

Values

Default:

Read Only

Min/Max:

0000/1911

Display:

0000

1 = Condition True, 0 = Condition False

Rx

Digit 1

Tx

Digit 2

Status

Digit 3

Error

Digit 4

Not Used

Digit 3 = “Internal Com option”

0

“Not Active (no connection)”

1

“Internal option connected/active”

2...8 “Reserved”

9

“Internal com option faulted”