Rockwell Automation Publication 520-UM001G-EN-E - September 2014

199

Velocity StepLogic, Basic Logic and Timer/Counter Functions

Appendix D

Transition to Step 2 when both Logic In 1 and Logic In 2 are true.
The drive senses the level of both Logic In 1 and Logic In 2 and transitions
to Step 2 when both are on.

Transition to Step 3 when Logic In 2 returns to a false or off state.
Inputs are not required to remain in the “on” condition except under the
logic conditions used for the transition from Step 2 to Step 3.

The step time value and the basic logic may be used together to satisfy machine
conditions. For instance, the step may need to run for a minimum time period
and then use the basic logic to trigger a transition to the next step.

Timer Function

Digital inputs and outputs control the timer function and are configured with
parameters t062...t063, t065...t068 [DigIn TermBlk xx] set to 19 “Timer Start”
and 21 “Reset Timer”.

Digital outputs (relay and opto type) define a preset level and indicate when the
level is reached. Level parameters t077 [Relay Out1 Level], t082[Relay Out2
Level], t070 [Opto Out1 Level] and t073 [Opto Out2 Level] are used to set the
desired time in seconds.

Parameters t076 [Relay Out1 Sel], t081 [Relay Out2 Sel], t069 [Opto Out1 Sel]
and t072 [Opto Out2 Sel] are set to 25 “Timer Out” and causes the output to
change state when the preset level is reached.

Example

Drive starts up and accelerates to 30 Hz.

After 30 Hz has been maintained for 20 seconds, a 4-20 mA analog input
becomes the reference signal for speed control.

Time

Logic In 1

Logic In 2

Frequency

Start

Step 0

Step 1

Step 2

Step 3

Time

Logic In 1

Logic In 2

Frequency

Start

Step 0

Step 1