Communications Group (continued)

C161 [Opt Data In 1]
C162 [Opt Data In 2]
C163 [Opt Data In 3]
C164 [Opt Data In 4]

Datalink parameter number whose value is written from the High Speed Drive Serial Interface (HSDSI) data table. This parameter cannot be changed when an I/O connection is
established through the communication adapter.

Values

Default:

0

Min/Max:

0/800

Display:

1

C165 [Opt Data Out 1]
C166 [Opt Data Out 2]
C167 [Opt Data Out 3]
C168 [Opt Data Out 4]

Datalink parameter number whose value is read from the HSDSI data table. This parameter cannot be changed when an I/O connection is established through the communication
adapter.

Values

Default:

0

Min/Max:

0/800

Display:

1

C169 [MultiDrv Sel]

Sets the configuration of the drive that is in multi-drive mode. A reset or power cycle is required after selection is made.

Options

0 “Disabled” (Default)

No multi-drive master from the internal network option module or embedded Ethernet port. The drive can still function as a
multi-drive slave or as a single drive (no multi-drive used).

1 “Network Opt”

Multi-drive is enabled with the internal network option as a multi-drive master. The host drive is “Drive 0” and up to four slave
drives can be daisy-chained from its RS485 port.

2 “EtherNet/IP”

(1)

Multi-drive is enabled with the embedded Ethernet port as the multi-drive master. The host drive is “Drive 0” and up to four slave
drives can be daisy-chained from its RS485 port.

(1) Setting is specific to PowerFlex 525 drives only.

C171 [Drv 1 Addr]

Related Parameter(s):

C169

C172 [Drv 2 Addr]
C173 [Drv 3 Addr]
C174 [Drv 4 Addr]

Sets the corresponding node addresses of the daisy-chained drives when

C169

[MultiDrv Sel] is set to 1 “Network Opt” or 2 “EtherNet/IP”. A reset or power cycle is required after

selection is made.

Values

Default:
Drv 1 Addr:
Drv 2 Addr:
Drv 3 Addr:
Drv 4 Addr:

2
3
4
5

Min/Max:

1/247

Display:

1

C175 [DSI I/O Cfg]

Sets the configuration of the Drives that are active in the multi-drive mode. Identifies the connections that would be attempted on a reset or power cycle. A reset or power cycle is
required after selection is made.

Options

0 “Drive 0” (Default)

1 “Drive 0-1”

2 “Drive 0-2”

3 “Drive 0-3”

4 “Drive 0-4”