A530, Advanced program group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 120

Advertising
background image

120

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 3

Programming and Parameters

Advanced Program Group (continued)

A530 [Boost Select]

Related Parameter(s):

b004

,

P031

,

P032

,

P039

Sets the boost voltage (% of

P031

[Motor NP Volts]) and redefines the V/Hz curve. Only used for V/Hz and SVC control modes.

Options

0 “Custom V/Hz”

1 “30.0, VT”

Fan/Pump Curves (Variable Torque)

2 “35.0, VT”

3 “40.0, VT”

4 “45.0, VT”

5 “0.0, no IR”

Boost Voltage (% of Base) (Constant Torque)

6 “0.0”

(Default for 400V and 600V
drives, 5 HP and above)

7 “2.5, CT”

(Default for 200V drives, 5 HP and
above)

8 “5.0, CT”

(Default for drives below 5 HP)

9 “7.5, CT”

10 “10.0, CT”

11 “12.5, CT”

12 “15.0, CT”

13 “17.5, CT”

14 “20.0, CT”

% [Motor NP Hertz]

% [Motor NP Volts]

100

50

1/2 [Motor NP Volts]

[Maximum Voltage] can be set anywhere.

If it is > [Motor NP Volts] then it defines a point on the V/Hz curve

[Maximum Freq] can be set anywhere.

If it is > [Motor NP Hertz] then it defines a

point on the V/Hz curve

[Maximum Voltage] can be set anywhere.

If it is < [Motor NP Volts] then it functions as a limit only

(does not change the V/Hz curve)

[Maximum Freq] can be set anywhere.

If it is < [Motor NP Hertz] then it functions as a limit only

(does not change the V/Hz curve)

1/2

[Motor NP Hertz]

4
3
2
1

0

50

100

Settings

5...14