Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 165

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

165

Accessories and Dimensions

Appendix B

(1) The resistors listed in this tables are rated for 5% duty cycle.
(2) Use of Rockwell Automation resistors is always recommended. The resistors listed have been carefully selected for optimizing

performance in a variety of applications. Alternative resistors may be used, however, care must be taken when making a selection.
See the PowerFlex Dynamic Braking Resistor Calculator, publication PFLEX-AT001.

(3) Requires two resistors wired in parallel.
(4) Requires three resistors wired in parallel.

200...240V
50/60 Hz
3-Phase

0.25

0.2

56

91

AK-R2-091P500

0.5

0.4

56

91

AK-R2-091P500

1.0

0.75

56

91

AK-R2-091P500

2.0

1.5

41

91

AK-R2-091P500

3.0

2.2

32

47

AK-R2-047P500

5.0

4.0

18

47

AK-R2-047P500

7.5

5.5

16

30

AK-R2-030P1K2

10.0

7.5

14

30

AK-R2-030P1K2

15.0

11.0

14

15

AK-R2-030P1K2

(3)

20.0

15.0

10

15

AK-R2-030P1K2

(3)

380...480V
50/60 Hz
3-Phase

0.5

0.4

89

360

AK-R2-360P500

1.0

0.75

89

360

AK-R2-360P500

2.0

1.5

89

360

AK-R2-360P500

3.0

2.2

89

120

AK-R2-120P1K2

5.0

4.0

47

120

AK-R2-120P1K2

7.5

5.5

47

120

AK-R2-120P1K2

10.0

7.5

47

120

AK-R2-120P1K2

15.0

11.0

43

60

AK-R2-120P1K2

(3)

20.0

15.0

43

60

AK-R2-120P1K2

(3)

25.0

18.5

27

40

AK-R2-120P1K2

(4)

30.0

22.0

27

40

AK-R2-120P1K2

(4)

525...600V
50/60 Hz
3-Phase

0.5

0.4

112

360

AK-R2-360P500

1.0

0.75

112

360

AK-R2-360P500

2.0

1.5

112

360

AK-R2-360P500

3.0

2.2

112

120

AK-R2-120P1K2

5.0

4.0

86

120

AK-R2-120P1K2

7.5

5.5

59

120

AK-R2-120P1K2

10.0

7.5

59

120

AK-R2-120P1K2

15.0

11.0

59

60

AK-R2-120P1K2

(3)

20.0

15.0

59

60

AK-R2-120P1K2

(3)

25.0

18.5

53

60

AK-R2-120P1K2

(3)

30.0

22.0

34

40

AK-R2-120P1K2

(4)

EMC Line Filters

Drive Ratings

Frame Size

Catalog No.

Input Voltage

HP

kW

Current (A)

100...120V
50/60 Hz
1-Phase

0.25

0.2

1.6

A

25-RF011-AL

0.5

0.4

2.5

A

25-RF011-AL

1.0

0.75

4.8

B

25-RF023-BL

1.5

1.1

6.0

B

25-RF023-BL

Dynamic Brake Resistors

Drive Ratings

Minimum
Resistance

±10%

Resistance

±5%

Catalog No.

(1)(2)

Input Voltage

HP

kW

Advertising
This manual is related to the following products: