Powerflex 523 control i/o terminal block, Powerflex 523 control i/o wiring block diagram – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 37

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

37

Installation/Wiring

Chapter 1

PowerFlex 523 Control I/O Terminal Block

PowerFlex 523 Control I/O Wiring Block Diagram

Control I/O Wiring Block Diagram Notes

(1) See

Digital Input Selection for Start Source on page 47

for more information on configuring the digital inputs.

IMPORTANT

I/O Terminal 01 is always a stop input. The stopping mode is determined by the
drive setting. See the tables below for more information.

Start Method

Stop Method

P046, P048, P050 [Start Source x]

I/O Terminal 01 Stop

Normal Stop

1 “Keypad”

Coast

Per P045
[Stop Mode]

2 “DigIn TrmBlk”

See

t062, t063 [DigIn TermBlk xx]

below

3 “Serial/DSI”

Coast

4 “Network Opt”

Coast

5 “Ethernet/IP”

(1)

(1) Setting is specific to PowerFlex 525 drives only.

Coast

04

05

06

01

02

03

11

12

13

14

15

C1

C2

Digital Common

DigIn TermBlk 05/Pulse

DigIn TermBlk 06

Stop

(1)

DigIn TermBlk 02/

Start/Run FWD

(2)

DigIn TermBlk 03/

Direction/Run REV

R1

R2

Relay N.O.

Relay Common

+24V DC

+10V DC

0-10V Input

Analog Common

4-20mA Input

RJ45 Shield

Comm Common

+24V

+10V

Typical

SNK wiring

Typical

SRC wiring

R1

11

12

13

14

15

C1

C2

R2

R3

01

02

03

04

05

06

Pot must be

1...10 k ohm

2 W min.

SNK

D

igital In

D

igIn

TermBlk 05 S

el

J7

J8

Pulse In

SRC

Digital

Input

SRC

SNK

R3

Relay N.C.

81

RS485

(DSI)