Rockwell Automation Publication 520-UM001G-EN-E - September 2014

57

Start Up

Chapter 2

16.

Verify the drive and motor perform as specified.

Verify that the Stop input is present or the drive will not start.

Verify the drive is receiving the speed reference from the correct place
and that the reference is scaled correctly.

Verify the drive is receiving start and stop commands correctly.

Verify input currents are balanced.

Verify motor currents are balanced.

17.

Save a backup of the drive settings using the USB utility application. See

Using the USB Port on page 63

for more information.

Start, Stop, Direction and Speed Control

Factory default parameter values allow the drive to be controlled from the
keypad. No programming is required to start, stop, change direction and control
speed directly from the keypad.

If a fault appears on power up, see

Fault Descriptions on page 147

for an

explanation of the fault code.

Variable Torque Fan/Pump Applications

For improved motor tuning performance when using a premium efficient motor
on a variable torque loading SVC mode, set A530 [Boost Select] to 2 “35.0, VT”.

IMPORTANT

If I/O Terminal 01 is used as a stop input, the jumper between I/O
Terminals 01 and 11 must be removed.

IMPORTANT

To disable reverse operation, see A544 [Reverse Disable].