Chapter 1

Installation/Wiring

Maximum Control Wire Recommendations

Do not exceed control wiring length of 30 m (100 ft). Control signal cable length
is highly dependent on electrical environment and installation practices. To
improve noise immunity, the I/O terminal block Common may be connected to
ground terminal/protective earth.

Control I/O Terminal Block

Recommended Signal Wire

Signal Type/
Where Used

Belden Wire Type(s)

(1)

(or equivalent)

(1) Stranded or solid wire.

Description

Min. Insulation
Rating

Analog I/O & PTC

8760/9460

0.750 mm

2

(18 AWG), twisted pair,

100% shield with drain

(2)

(2) If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be necessary,

but is always recommended.

300V,
60

°C (140 °F)

Remote Pot

8770

0.750 mm

2

(18 AWG), 3 conductor, shielded

Encoder/Pulse I/O

9728/9730

0.196 mm

2

(24 AWG), individually shielded pairs

Recommended Control Wire for Digital I/O

Type

Wire Type(s)

Description

Min. Insulation
Rating

Unshielded

Per US NEC or applicable
national or local code

300V,
60

°C (140 °F)

Shielded

Multi-conductor shielded
cable such as Belden 8770
(or equivalent)

0.750 mm

2

(18 AWG), 3 conductor, shielded.

Control I/O Terminal Block Wire Specifications

Frame

Maximum Wire Size

(1)

(1) Maximum/minimum sizes that the terminal block will accept – these are not recommendations.

Minimum Wire Size

(1)

Torque

A...E

1.3 mm

2

(16 AWG)

0.13 mm

2

(26 AWG)

0.71...0.86 Nm (6.2...7.6 lb-in.)