Chapter 1

Installation/Wiring

(2) Two wire control shown. For three wire control use a momentary input

on I/O Terminal 02 to command a start. Use a

maintained input

for I/O Terminal 03 to change direction.

Start Method

Stop Method

t062, t063 [DigIn TermBlk xx]

I/O Terminal 01 Stop

Normal Stop

48 “2-Wire FWD”

t064 [2-Wire Mode] is set to:
0, 1, or 2 = Coast
3 = per P045 [Stop Mode]

Per P045
[Stop Mode]

49 “3-Wire Start”

Per P045 [Stop Mode]

50 “2-Wire REV”

t064 [2-Wire Mode] is set to:
0, 1, or 2 = Coast
3 = per P045 [Stop Mode]

51 “3-Wire Dir”

Per P045 [Stop Mode]

IMPORTANT

The drive is shipped with a jumper installed between I/O Terminals 01 and 11.
Remove this jumper when using I/O Terminal 01 as a stop or enable input.

Control I/O Terminal Designations

No. Signal

Default

Description

Parameter

R1 Relay N.O.

Fault

Normally open contact for output relay.

t076

R2 Relay Common

Fault

Common for output relay.

R3 Relay N.C.

Motor Running Normally closed contact for output relay.

t081

01

Stop

Coast

Three wire stop. However, it functions as a stop under all input
modes and cannot be disabled.

P045

(2)

02

DigIn TermBlk 02/
Start/Run FWD

Run FWD

Used to initiate motion and also can be used as a programmable
digital input. It can be programmed with t062 [DigIn TermBlk
02] as three wire (Start/Dir with Stop) or two wire (Run FWD/
Run REV) control. Current consumption is 6 mA.

P045

,

P046

,

P048

,

P050

,

A544

,

t062

03

DigIn TermBlk 03/
Dir/Run REV

Run REV

Used to initiate motion and also can be used as a programmable
digital input. It can be programmed with t063 [DigIn TermBlk
03] as three wire (Start/Dir with Stop) or two wire (Run FWD/
Run REV) control. Current consumption is 6 mA.

t063

04

Digital Common

Return for digital I/O. Electrically isolated (along with the digital
I/O) from the rest of the drive.

05

DigIn TermBlk 05/
Pulse In

Preset Freq

Program with t065 [DigIn TermBlk 05]. Also functions as a Pulse
Train input for reference or speed feedback. The maximum
frequency is 100 kHz. Current consumption is 6 mA.

t065

06

DigIn TermBlk 06 Preset Freq

Program with t066 [DigIn TermBlk 06].
Current consumption is 6 mA.

t066

11

+24V DC

Referenced to Digital Common.
Drive supplied power for digital inputs.
Maximum output current is 100 mA.

12

+10V DC

Referenced to Analog Common.
Drive supplied power for 0...10V external potentiometer.
Maximum output current is 15 mA.

P047

,

P049

13

0-10V In

(1)

Not Active

For external 0-10V (unipolar) input supply or potentiometer
wiper.
Input impedance:

Voltage source = 100 k

Allowable potentiometer resistance range = 1...10 k

P047

,

P049

,

t062

,

t063

,

t065

,

t066

,

t093

,

A459

,

A471

14

Analog Common

Return for the analog I/O. Electrically isolated (along with the
analog I/O) from the rest of the drive.