Start and speed reference control, Start source and speed reference selection – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 46

Advertising
background image

46

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 1

Installation/Wiring

Start and Speed Reference
Control

Start Source and Speed Reference Selection

The start and drive speed command can be obtained from a number of different
sources. By default, start source is determined by

P046

[Start Source 1] and drive

speed source is determined by

P047

[Speed Reference1]. However, various inputs

can override this selection, See below for the override priority.

(1) [Start Source 2/3] and [Speed Reference2/3] can be selected by the control terminal block or communication commands.
(2) See

Digital Input Selection for Start Source on page 47

for information on selecting the correct digital input.

Purge Input Enabled

AND Active

Jog Input Enabled

AND Active

Preset Inputs Active

[Speed Referencex]

= 11 or 12 (PIDx Output)

AND

[PID x Ref Sel]

= 7 (Preset Freq)

[Speed Reference3]

select

(1)

[Start Source 3]

select

(1)

[Start Source 2]

select

(1)

[Speed Reference2]

select

(1)

Drive stopped

(NOT running)

Drive will start and

run at Purge Speed.

Direction is always

FORWARD.

Drive will start and run at

Jog Speed.

Direction is from Terminal

Block REV terminal (03),

Comms,

OR

FWD/REV determined by

Jog FWD/Jog REV command.

Run as specified by

[PIDx Output].

Start and Direction

commands come from

[Start Source x].

Run as specified by

[Preset Freq x].

Start and Direction

commands come from

[Start Source x].

Run as specified by

[Speed Reference3].

Run as specified by

[Speed Reference2].

Run as specified by

[Speed Reference1].

Start and Direction

command from

[Start Source 1].

Start and Direction

command from

[Start Source 3].

(2)

No

No

No

No

No

No

No

No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Start and Direction

command from

[Start Source 2].

(2)

Yes

Advertising