C146, C147, C150 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 98: Communications group (continued)

Advertising
background image

98

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 3

Programming and Parameters

Communications Group (continued)

C146 [EN Flt Cfg Ref]

Related Parameter(s):

C143

,

C144

32 bit parameter.

PowerFlex 525 only.

Sets the Reference data that is sent to the drive if any of the following is true:

C143

[EN Comm Flt Actn] is set to 4 “Send Flt Cfg” and communications are disrupted.

C144

[EN Idle Flt Actn] is set to 4 “Send Flt Cfg” and the scanner is put into Program or Test mode.

Values

Default:

0

Min/Max:

0/50000

Display:

1

32

PF 525

C147 [EN Flt Cfg DL 1]
C148 [EN Flt Cfg DL 2]
C149 [EN Flt Cfg DL 3]
C150 [EN Flt Cfg DL 4]

PowerFlex 525 only.

Sets the Ethernet Datalink Input data that is sent to the drive if any of the following is true:

C143

[EN Comm Flt Actn] is set to 4 “Send Flt Cfg” and communications are disrupted.

C144

[EN Idle Flt Actn] is set to 4 “Send Flt Cfg” and the scanner is put into Program or Test mode.

Values

Default:

0

Min/Max:

0/65535

Display:

1

PF 525

C153 [EN Data In 1]
C154 [EN Data In 2]
C155 [EN Data In 3]
C156 [EN Data In 4]

PowerFlex 525 only.

Datalink parameter number whose value is written from the embedded EtherNet/IP data table. This parameter cannot be changed when an I/O connection is established through the
drive’s embedded EtherNet/IP port.

Values

Default:

0

Min/Max:

0/800

Display:

1

PF 525

C157 [EN Data Out 1]
C158 [EN Data Out 2]
C159 [EN Data Out 3]
C160 [EN Data Out 4]

PowerFlex 525 only.

Datalink parameter number whose value is read from the embedded EtherNet/IP data table. This parameter cannot be changed when an I/O connection is established through the
drive’s embedded EtherNet/IP port.

Values

Default:

0

Min/Max:

0/800

Display:

1

PF 525