Advanced Program Group (continued)

A433 [Purge Frequency]

Related Parameter(s):

t062

,

t063

,

t065

-

t068

Provides a fixed frequency command value when

t062

,

t063

,

t065

-

t068

[DigIn TermBlk xx] is set to 40 “Purge”.

Values

Default:

5.00 Hz

Min/Max:

0.00/500.00 Hz

Display:

0.01 Hz

A434 [DC Brake Time]

Related Parameter(s):

P045

,

A435

Sets the length of time that DC brake current is “injected” into the motor.

Values

Default:

0.0 s

Min/Max:

0.0/99.9 s

Display:

0.1 s

A435 [DC Brake Level]

Related Parameter(s):

P045

Defines the maximum DC brake current, in amps, applied to the motor when

P045

[Stop Mode] is set to either 4 “Ramp” or 6 “DC Brake”.

Values

Default:

Drive Rated Amps x 0.05

Min/Max:

0.00/(Drive Rated Amps x 1.80)

Display:

0.01 A

DC Injection Stop Mode

Volts/Speed

Voltage

Time

Stop Command

Speed

[DC Brake Time]

Volts/Speed

Ramp-to-Stop Mode

Time

Stop Command

Magnitude
depends on
[DC Brake Level]

Magnitude
depends on
[DC Brake Level]

[DC Brake Time]

Voltage

Speed

ATTENTION: If a hazard of injury due to movement of equipment or material exists, an auxiliary mechanical braking device must be used. This feature should
not be used with synchronous motors. Motors may be demagnetized during braking.

A436 [DC Brk Time@Strt]

Related Parameter(s):

P045

,

A435

Sets the length of time that DC brake current is “injected” into the motor after a valid start command is received.

Values

Default:

0.0 s

Min/Max:

0.0/99.9 s

Display:

0.1 s

Volts/Speed

Time

Start Command

[DC Brake Level]

[DC Brk Time@Strt]

Voltage

Speed