Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual
Page 194

194
Rockwell Automation Publication 520-UM001G-EN-E - September 2014
Appendix C
RS485 (DSI) Protocol
Velocity Bit Definitions
Comm Logic Status – C122 = 0 “Velocity”
Address (Decimal)
Bit(s)
Description
2100H (8448)
0
1 = Ready, 0 = Not Ready
1
1 = Active (Running), 0 = Not Active
2
1 = Cmd Forward, 0 = Cmd Reverse
3
1 = Rotating Forward, 0 = Rotating Reverse
4
1 = Accelerating, 0 = Not Accelerating
5
1 = Decelerating, 0 = Not Decelerating
6
Not Used
7
1 = Faulted, 0 = Not Faulted
8
1 = At Reference, 0 = Not At Reference
9
1 = Main Freq Controlled by Active Comm
10
1 = Operation Cmd Controlled by Active Comm
11
1 = Parameters have been locked
12
Digital Input 1 Status
13
Digital Input 2 Status
14
Digital Input 3 Status
15
Digital Input 4 Status
Position Bit Definitions
Comm Logic Status – C122 = 1 “Position”
Address (Decimal)
Bit(s)
Description
2100H (8448)
0
1 = Ready, 0 = Not Ready
1
1 = Active (Running), 0 = Not Active
2
1 = Cmd Forward, 0 = Cmd Reverse
3
1 = Rotating Forward, 0 = Rotating Reverse
4
1 = Accelerating, 0 = Not Accelerating
5
1 = Decelerating, 0 = Not Decelerating
6
1 = Forward Travel Position, 0 = Reverse Travel Position
7
1 = Faulted, 0 = Not Faulted
8
1 = At Reference, 0 = Not At Reference
9
1 = At Position, 0 = Not At Position
10
1 = At Home, 0 = Not At Home
11
1 = Drive Homed, 0 = Not Drive Homed
12
1 = Sync Hold, 0 = Not Sync Hold
13
1 = Sync Ramp, 0 = Not Sync Ramp
14
1 =Traverse On, 0 = Traverse Off
15
1 = Traverse Decel, 0 = Not Traverse Decel