194

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Appendix C

RS485 (DSI) Protocol

Velocity Bit Definitions

Comm Logic Status – C122 = 0 “Velocity”

Address (Decimal)

Bit(s)

Description

2100H (8448)

0

1 = Ready, 0 = Not Ready

1

1 = Active (Running), 0 = Not Active

2

1 = Cmd Forward, 0 = Cmd Reverse

3

1 = Rotating Forward, 0 = Rotating Reverse

4

1 = Accelerating, 0 = Not Accelerating

5

1 = Decelerating, 0 = Not Decelerating

6

Not Used

7

1 = Faulted, 0 = Not Faulted

8

1 = At Reference, 0 = Not At Reference

9

1 = Main Freq Controlled by Active Comm

10

1 = Operation Cmd Controlled by Active Comm

11

1 = Parameters have been locked

12

Digital Input 1 Status

13

Digital Input 2 Status

14

Digital Input 3 Status

15

Digital Input 4 Status

Position Bit Definitions

Comm Logic Status – C122 = 1 “Position”

Address (Decimal)

Bit(s)

Description

2100H (8448)

0

1 = Ready, 0 = Not Ready

1

1 = Active (Running), 0 = Not Active

2

1 = Cmd Forward, 0 = Cmd Reverse

3

1 = Rotating Forward, 0 = Rotating Reverse

4

1 = Accelerating, 0 = Not Accelerating

5

1 = Decelerating, 0 = Not Decelerating

6

1 = Forward Travel Position, 0 = Reverse Travel Position

7

1 = Faulted, 0 = Not Faulted

8

1 = At Reference, 0 = Not At Reference

9

1 = At Position, 0 = Not At Position

10

1 = At Home, 0 = Not At Home

11

1 = Drive Homed, 0 = Not Drive Homed

12

1 = Sync Hold, 0 = Not Sync Hold

13

1 = Sync Ramp, 0 = Not Sync Ramp

14

1 =Traverse On, 0 = Traverse Off

15

1 = Traverse Decel, 0 = Not Traverse Decel

Advertising