Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 54

Advertising
background image

54

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 1

Installation/Wiring

Recommended Placement of EMC Cores

Frame A

Frame B

Frame C

Frame D

Frame E

With optional EMC plate (25-EMC-Fx)

Without EMC plate

CORE-xx-A-1

CORE-xx-A-2

CORE-xx-B-1

CORE-xx-B-2

CORE-xx-C-1

CORE-xx-C-2

CORE-xx-D-1

CORE-xx-D-2

CORE-E-1

CORE-E-2

CORE-E-3

CORE-E-4

Ground
cable

CORE-xx-x-1

CORE-xx-x-2

CORE-E-1

CORE-E-2

CORE-E-3

CORE-E-4

Ground
cable

Shows contact to
shielded layer

Secure EMC core by
using cable/zip ties

Output cable from drive (Shielded)

Input cable to drive (Shielded or Unshielded)

IMPORTANT

The ground cable/shield for both input and output must pass through the EMC core(s), except for the following:

Frame E drives with internal filters where the grounded input cable must not pass through EMC CORE-E-1.
600V drives with external filters where the grounded output cable must not pass through the EMC core(s).

Recommended Placement of EMC Cores Relative to External Filter

Input core

Output core

Incoming power

EMC Filter

Drive

Motor

All Frame sizes