Circuit status, Operating principle, Fault detection – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 231

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

231

Safe-Torque-Off Function

Appendix G

Example 2 – Safe-Torque-Off Connection with Controlled Stop Action,
SIL 2/PL d

Stop Category 1 – Controlled

(1) Enclosure Recommended. External wiring failure modes must be considered as described in EN ISO 13849-2. Enclosure or other

measure to exclude these failure modes should be used.

Circuit Status

Circuit shown with guard door closed and system ready for normal drive
operation.

Operating Principle

This is a dual channel system with monitoring of the Safe-Torque-Off circuit and
drive. Opening the guard door will switch the input circuits (S11-S12 & S21-
S22) to the Minotaur monitoring safety relay unit. The output circuits (13-14)
will issue a Stop command to the drive and cause a controlled deceleration. After
the programmed delay, the timed output circuits (47-48 & 57-58) will cause the
Safe-Torque-Off Enable circuit to trip. If the motor is rotating when the trip
occurs, it will coast to stop. To restart the drive, the Minotaur safety relay must
first be reset followed by a valid start command to the drive.

Fault Detection

A single fault detected on the Minotaur safety input circuits will result in the
lock-out of the system at the next operation and will not cause loss of the safety
function.

A single fault detected on the PowerFlex 525 safety enable redundant inputs will
result in the lock-out of the drive and will not cause the loss of the safety
function.

24V DC

Common

+24V DC

GuardMaster

Trojan

Stop

Start

A1

S21 S11 S52 S12

A2 X1 X2

13 23

14 24

S33

Y2

S34

Y1

X3

37 47 57

38 48 58

X4

S22

Y39 Y40

Minotaur

MSR138DP

Gate

+24V DC

PF 525

Stop

Start

Gate control

power supply

Gate control

circuit

AC line

input power

S1

S2

M

(1)

Advertising
This manual is related to the following products: