Programming and Parameters

Chapter 3

Advanced Program Group (continued)

A490 [Load Loss Level]

Related Parameter(s):

A491

PowerFlex 525 only.

Provides a software trip (Load Loss fault) when the current drops below this level for the time specified in

A491

[Load Loss Time].

Values

Default:

0.0 A

Min/Max:

0.0/Drive Rated Amps

Display:

0.1 A

PF 525

A491 [Load Loss Time]

Related Parameter(s):

A490

PowerFlex 525 only.

Sets the required time for the current to be below

A490

[Load Loss Level] before a Load Loss fault occurs.

Values

Default:

0 s

Min/Max:

0/9999 s

Display:

1 s

PF 525

A492 [Stall Fault Time]

Sets the time that the drive remains in stall mode before a fault is issued.

Options

0 “60 Seconds” (Default)

1 “120 Seconds”

2 “240 Seconds”

3 “360 Seconds”

4 “480 Seconds”

5 “Flt Disabled”

A493 [Motor OL Select]

Related Parameter(s):

P032

,

P033

Drive provides Class 10 overload protection. Settings 0...2 select the derating factor for the I

2

t overload function.

Options

0 “No Derate” (Default)

1 “Min. Derate”

2 “Max. Derate”

Min Derate

0

80

100

60

40

20

% of [Motor OL Curent]

No Derate

0

80

100

60

40

20

% of [Motor NP Hertz]

% of [Motor OL Curent]

% of [Motor NP Hertz]

% of [Motor OL Curent]

% of [Motor NP Hertz]

Max Derate

0

80

100

60

40

20

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

0

200

175

150

125

100

75

50

25

A494 [Motor OL Ret]

Selects whether the motor overload counter is saved on power-down or reset on power-up.

Options

0 “Reset” (Default)

1 “Save”