Chapter 4

Troubleshooting

F015

(1)

Load Loss

2

The output torque current is below the
value programmed in

A490

[Load Loss

Level] for a time period greater than the
time programmed in

A491

[Load Loss

Time].

Verify connections between motor

and load.

Verify level and time requirements

F021

Output Ph Loss

1

Output Phase Loss (if enabled).
Configure with

A557

[Out Phas Loss En].

Verify motor wiring.
Verify motor.

F029

Analog In Loss

1

An analog input is configured to fault on
signal loss. A signal loss has occurred.
Configure with

t094

[Anlg In V Loss] or

t097

[Anlg In mA Loss].

Check for broken/loose connections

at inputs.

Check parameters.

F033

Auto Rstrt Tries

2

Drive unsuccessfully attempted to reset
a fault and resume running for the
programmed number of

A541

[Auto

Rstrt Tries].

Correct the cause of the fault and
manually clear.

F038

Phase U to Gnd

2

A phase to ground fault has been
detected between the drive and motor
in this phase.

Check the wiring between the drive

and motor.

Check motor for grounded phase.
Replace drive if fault cannot be

cleared.

F039

Phase V to Gnd

F040

Phase W to Gnd

F041

Phase UV Short

2

Excessive current has been detected
between these two output terminals.

Check the motor and drive output

terminal wiring for a shorted
condition.

Replace drive if fault cannot be

cleared.

F042

Phase UW Short

F043

Phase VW Short

F048

Params Defaulted 1

The drive was commanded to write
default values to EEPROM.

Clear the fault or cycle power to the

drive.

Program the drive parameters as

needed.

F059

(1)

Safety Open

1

Both of the safety inputs (Safety 1,
Safety 2) are not enabled.
Configure with

t105

[Safety Open En].

Check safety input signals. If not

using safety, verify and tighten
jumper for I/O terminals S1, S2 and
S+.

F063

SW OverCurrent

1

Programmed

A486

,

A488

[Shear Pinx

Level] has been exceeded for a time
period greater than the time
programmed in

A487

,

A489

[Shear Pin x

Time].

Verify connections between motor

and load.

Verify level and time requirements.

F064

Drive Overload

2

Drive overload rating has been
exceeded.

Reduce load or extend Accel Time.

F070

Power Unit

2

Failure has been detected in the drive
power section.

Check maximum ambient

temperature has not been exceeded.

Cycle power.
Replace drive if fault cannot be

cleared.

F071

DSI Net Loss

2

Control over the Modbus or DSI
communication link has been
interrupted.

Cycle power.
Check communications cabling.
Check Modbus or DSI setting.
Check Modbus or DSI status.

F072

Opt Net Loss

2

Control over the network option card’s
remote network has been interrupted.

Cycle power.
Check communications cabling.
Check network adapter setting.
Check external network status.

F073

(1)

EN Net Loss

2

Control through the embedded
EtherNet/IP adapter has been
interrupted.

Cycle power.
Check communications cabling.
Check EtherNet/IP setting.
Check external network status.

F080

Autotune Failure

2

The autotune function was either
cancelled by the user or failed.

Restart procedure.

Fault Types, Descriptions and Actions

No.

Fault

Type

(2)

Description

Action