A567, A571, Advanced program group (continued) – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 128

Advertising
background image

128

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 3

Programming and Parameters

Advanced Program Group (continued)

A567 [Max Traverse]

Sets the amplitude of triangle wave speed modulation.

Values

Default:

0.00 Hz

Min/Max:

0.00/300.00 Hz

Display:

0.01 Hz

Her

tz

Seconds

[Max Traverse]

[P Jump]

[Output Freq]

[Fiber Status]

Traverse Enable Bit

Traverse Bit

A568 [Traverse Inc]

Related Parameter(s):

A567

Sets the time required for the Traverse function to accelerate from the minimum to the maximum traverse frequency. See the diagram at

A567

[Max Traverse].

Values

Default:

0.00 s

Min/Max:

0.00/300.00 s

Display:

0.01 s

A569 [Traverse Dec]

Related Parameter(s):

A567

Sets the time required for the Traverse function to decelerate from the maximum to the minimum traverse frequency. See the diagram at

A567

[Max Traverse].

Values

Default:

0.00 s

Min/Max:

0.00/300.00 s

Display:

0.01 s

A570 [P Jump]

Related Parameter(s):

A567

Sets the frequency amplitude that is added to or subtracted from the commanded frequency. See the diagram at

A567

[Max Traverse].

Values

Default:

0.00 Hz

Min/Max:

0.00/300.00 Hz

Display:

0.01 Hz

A571 [Sync Time]

Related Parameter(s):

t062

,

t063

,

t065

-

t068

,

A560

Enables the function that holds the drive at the current frequency even if the commanded frequency changes. Used with

t062

,

t063

,

t065

-

t068

[DigIn TermBlk xx] 32 “Sync Enable”.

Values

Default:

0.0 s

Min/Max:

0.0/3200.0 s

Display:

0.1 s

Hertz

Time

Speed Sync Bit

Change Ref's

[Sync Time]

Drive #1 and #2 Sync Enable Input

[Fiber Status]

New Drive #1 Reference

New Drive #2 Reference