Rockwell Automation Publication 520-UM001G-EN-E - September 2014

77

Programming and Parameters

Chapter 3

Basic Program Group (continued)

P034 [Motor NP FLA]

Related Parameter(s):

P040

Sets the motor nameplate FLA. Used to assist the Autotune routine and motor control.

Values

Default:

Based on Drive Rating

Min/Max:

0.1/(Drive Rated Amps x 2)

Display:

0.1 A

P035 [Motor NP Poles]

Related Parameter(s):

b015

Sets the number of poles in the motor.

Values

Default:

4

Min/Max:

2/40

Display:

1

P036 [Motor NP RPM]

Stop drive before changing this parameter.

Sets the rated nameplate rpm of the motor. Used to calculate the rated slip of the motor. To reduce the slip frequency, set this parameter closer to the motor synchronous speed.

Values

Default:

1750 rpm

Min/Max:

0/24000 rpm

Display:

1 rpm

P037 [Motor NP Power]

PowerFlex 525 only.

Sets the motor nameplate power. Used in PM regulator.

Values

Default:

Drive Rated Power

Min/Max:

0.00/Drive Rated Power

Display:

0.01 kW

PF 525

P038 [Voltage Class]

Stop drive before changing this parameter.

Sets the voltage class of 600V drives. Only applicable to 600V drives.

Options

2 “480V”

3 “600V” (Default)

P039 [Torque Perf Mode]

Related Parameter(s):

P040

,

A530

,

A531

,

A532

,

A533

Stop drive before changing this parameter.

Selects the motor control mode.

Options

0 “V/Hz”

1 “SVC” (Default)

2 “Economize”

3 “Vector”

(1)

(1) Setting is specific to PowerFlex 525 drives only.