Basic Program Group (continued)

P043 [Minimum Freq]

Related Parameter(s):

b001

,

b002

,

b013

,

P044

,

A530

,

A531

Stop drive before changing this parameter.

Sets the lowest frequency the drive outputs.

Values

Default:

0.00 Hz

Min/Max:

0.00/500.00 Hz

Display:

0.01 Hz

P044 [Maximum Freq]

Related Parameter(s):

b001

,

b002

,

b013

,

b016

,

P043

,

A530

,

A531

Stop drive before changing this parameter.

Sets the highest frequency the drive outputs.

Values

Default:

60.00 Hz

Min/Max:

0.00/500.00 Hz

Display:

0.01 Hz

IMPORTANT

This value must be greater than the value set in P043 [Minimum Freq].

P045 [Stop Mode]

Related Parameter(s):

t086

,

t087

,

A434

,

A435

,

A550

Determines the stopping mode used by the drive when a stop is initiated.

Options

0 “Ramp, CF” (Default)

Ramp to Stop. Stop command clears active fault.

1 “Coast, CF”

Coast to Stop. Stop command clears active fault.

2 “DC Brake, CF”

DC Injection Braking Stop. Stop command clears active fault.

3 “DC BrkAuto,CF”

DC Injection Braking Stop with Auto Shutoff.
Standard DC Injection Braking for value set in

A434

[DC Brake Time].

OR

Drive shuts off if the drive detects that the motor is stopped.
Stop command clears active fault.

4 “Ramp”

Ramp to Stop.

5 “Coast”

Coast to Stop.

6 “DC Brake”

DC Injection Braking Stop.

7 “DC BrakeAuto”

DC Injection Braking Stop with Auto Shutoff.
Standard DC Injection Braking for value set in

A434

[DC Brake Time].

OR

Drive shuts off if the drive detects that the motor is stopped.

8 “Ramp+EM B,CF”

Ramp to Stop with EM Brake Control. Stop command clears active fault.

9 “Ramp+EM Brk”

Ramp to Stop with EM Brake Control.

10 “PointStp,CF”

PointStop. Stop command clears
active fault.

Provides a method to stop at a constant distance instead of a fixed rate.
When a Stop command is given, the distance required for the machine to travel to
standstill based on the programmed maximum speed and deceleration time is calculated.
If the drive is running slower than the maximum speed, the function will apply a calculated
deceleration time that allows the machine to travel to standstill in the same distance based
on the current speed.
It is recommended to use braking resistors or set

A550

[Bus Reg Enable] to 0 “Disabled” for

better performance.

11 “PointStop”

PointStop.

Speed

Time

[Maximum Freq]

Stop

Calculated Stop Time

[Decel Time x]