C127 [RS485 Format]

Determines the details related to the specific Modbus protocol used by the drive. A reset or power cycle is required after selection is made.

Options

0 “RTU 8-N-1” (Default)

1 “RTU 8-E-1”

2 “RTU 8-O-1”

3 “RTU 8-N-2”

4 “RTU 8-E-2”

5 “RTU 8-O-2”

C128 [EN Addr Sel]

Related Parameter(s):

C129

-

C132

,

C133

-

C136

,

C137

-

C140

PowerFlex 525 only.

Enables the IP address, subnet mask and gateway address to be set with a BOOTP server. Identifies the connections that would be attempted on a reset or power cycle. A reset or power
cycle is required after selection is made.

Options

1 “Parameters”

2 “BOOTP” (Default)

PF 525

C129 [EN IP Addr Cfg 1]

Related Parameter(s):

C128

C130 [EN IP Addr Cfg 2]
C131 [EN IP Addr Cfg 3]
C132 [EN IP Addr Cfg 4]

PowerFlex 525 only.

Sets the bytes in the IP address. A reset or power cycle is required after selection is made.

Values

Default:

0

Min/Max:

0/255

Display:

1

PF 525

192.168.1.62

[EN IP Addr Cfg 1]

[EN IP Addr Cfg 2]

[EN IP Addr Cfg 3]

[EN IP Addr Cfg 4]

IMPORTANT

C128 [EN Addr Sel] must be set to 1 “Parameters”.