C133, C136, C137 – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 96: C140, Communications group (continued)

Advertising
background image

96

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 3

Programming and Parameters

Communications Group (continued)

C133 [EN Subnet Cfg 1]

Related Parameter(s):

C128

C134 [EN Subnet Cfg 2]
C135 [EN Subnet Cfg 3]
C136 [EN Subnet Cfg 4]

PowerFlex 525 only.

Sets the bytes of the subnet mask. A reset or power cycle is required after selection is made.

Values

Default:

0

Min/Max:

0/255

Display:

1

PF 525

255.255.255.0

[EN Subnet Cfg 1]

[EN Subnet Cfg 2]

[EN Subnet Cfg 3]

[EN Subnet Cfg 4]

IMPORTANT

C128 [EN Addr Sel] must be set to 1 “Parameters”.

C137 [EN Gateway Cfg 1]

Related Parameter(s):

C128

C138 [EN Gateway Cfg 2]
C139 [EN Gateway Cfg 3]
C140 [EN Gateway Cfg 4]

PowerFlex 525 only.

Sets the bytes of the gateway address. A reset or power cycle is required after selection is made.

Values

Default:

0

Min/Max:

0/255

Display:

1

PF 525

192.168.1.1

[EN Gateway Cfg 1]

[EN Gateway Cfg 2]

[EN Gateway Cfg 3]

[EN Gateway Cfg 4]

IMPORTANT

C128 [EN Addr Sel] must be set to 1 “Parameters”.

C141 [EN Rate Cfg]

PowerFlex 525 only.

Sets the network data rate at which EtherNet/IP communicates. A reset or power cycle is required after selection is made.

Options

0 “Auto detect” (Default)

1 “10Mbps Full”

2 “10Mbps Half”

3 “100Mbps Full”

4 “100Mbps Half”

PF 525