Programming and Parameters

Chapter 3

Basic Display Group (continued)

b013 [Contrl In Status]

Related Parameter(s):

b002

,

P044

,

P045

State of the digital terminal blocks 1...3 and DB transistor.

Values

Default:

Read Only

Min/Max:

0000/1111

Display:

0000

IMPORTANT

Actual control commands may come from a source other than the control terminal block.

1 = Closed State, 0 = Open State

DigIn TBlk 1

Digit 1

DigIn TBlk 2

Digit 2

DigIn TBlk 3

Digit 3

DB Trans On

(1)

Digit 4

(1)

The DB Transistor “on” indication must have a 0.5 s hysteresis. It will turn on and stay
on for at least 0.5 s every time the DB transistor is turned on.

Not Used

b014 [Dig In Status]

Related Parameter(s):

t065

-

t068

State of the programmable digital inputs.

Values

Default:

Read Only

Min/Max:

0000/1111

Display:

0000

1 = Closed State, 0 = Open State

DigIn TBlk 5

Digit 1

DigIn TBlk 6

Digit 2

DigIn TBlk 7

(1)

Digit 3

(1)

Setting is specific to PowerFlex 525 drives only.

DigIn TBlk 8

(1)

Digit 4

Not Used

b015 [Output RPM]

Related Parameter(s):

P035

Current output frequency in rpm. Scale is based on

P035

[Motor NP Poles].

Values

Default:

Read Only

Min/Max:

0/24000 rpm

Display:

1 rpm

b016 [Output Speed]

Related Parameter(s):

P044

Current output frequency in %. Scale is 0% at 0.00 Hz to 100% at

P044

[Maximum Freq].

Values

Default:

Read Only

Min/Max:

0.0/100.0%

Display:

0.1%

b017 [Output Power]

Related Parameter(s):

b018

Output power present at T1, T2 & T3 (U, V & W).

Values

Default:

Read Only

Min/Max:

0.00/(Drive Rated Power x 2)

Display:

0.01 kW