Adjusting speed control parameters – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 238

Advertising
background image

238

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Appendix I

Control Diagrams

Adjusting Speed Control
Parameters

These settings show how to adjust the speed control for motor tuning.

Run

Speed Loop Bandwidth:

A511 [Freq 1 BW] = 10 Hz
A513 [Freq 2 BW] = 10 Hz
A515 [Freq 3 BW] = 10 Hz

Set Speed Controller Gain

automatically

A509 = 0 (Automatic)

A509 = 1 (Manual)

Set Speed Controller Gain
manually:
A521 [Freq 1 Kp]
A522 [Freq 1 Ki]
A523 [Freq 2 Kp]
A524 [Freq 2 Ki]
A525 [Freq 3 Kp]
A526 [Freq 3 Ki]

Increase the bandwidth to obtain
faster speed response. If oscillation
occurs, decrease the bandwidth.

For general use, set A509
[Speed Reg Sel] to 0 (Automatic)

Set A509

[Speed Reg Sel]

For [Freq x Kp], gradually increase by 1%
For [Freq x Ki], gradually increase by 0.1 s