Velocity steplogic parameters – Rockwell Automation 25B PowerFlex 520-Series Adjustable Frequency AC Drive User Manual User Manual

Page 201

Advertising
background image

Rockwell Automation Publication 520-UM001G-EN-E - September 2014

201

Velocity StepLogic, Basic Logic and Timer/Counter Functions

Appendix D

Velocity StepLogic
Parameters

DigIn TermBlk 06

Reset Counter

Limit Switch

DigIn TermBlk 05

Counter In

Photo Eye

Start

Output

Frequency

Relay Out

Code Descriptions for Parameters L180...L187

Digit 4

Digit 3

Digit 2

Digit 1

0

0

F

1

Digit 4 – Defines the action during the step currently executing

Setting

Accel/Decel Parameter
Used

StepLogic Output State

Commanded Direction

0

1

Off

FWD

1

1

Off

REV

2

1

Off

No Output

3

1

On

FWD

4

1

On

REV

5

1

On

No Output

6

2

Off

FWD

7

2

Off

REV

8

2

Off

No Output

9

2

On

FWD

A

2

On

REV

b

2

On

No Output

Digit 3 – Defines what step to jump to or how to end program when the logic conditions specified
in Digit 2 are met.

Setting

Logic

0

Jump to Step 0

1

Jump to Step 1

2

Jump to Step 2

3

Jump to Step 3

4

Jump to Step 4

5

Jump to Step 5

6

Jump to Step 6

7

Jump to Step 7

8

End Program (Normal Stop)

9

End Program (Coast to Stop)

A

End Program and Fault (F002)