Rockwell Automation Publication 520-UM001G-EN-E - September 2014

Chapter 3

Programming and Parameters

Basic Program Group

P030 [Language]

Language Support

Selects the language displayed. A reset or power cycle is required after selection is made.

Keypad/
LCD Display

RSLogix 5000/
Logix Designer

Connected
Components
Workbench

Options

1 English (Default)

Y

Y

Y

2 Français

Y

Y

Y

3 Español

Y

Y

Y

4 Italiano

Y

Y

Y

5 Deutsch

Y

Y

Y

6 Japanese

Y

7 Português

Y

Y

8 Chinese

Chinese Simplified

Y

Y

9 Reserved

10 Reserved

11 Korean

Y

12 Polish

(1)

Y

13 Reserved

14 Turkish

(1)

Y

15 Czech

(1)

Y

(1) Due to a limitation of the LCD Display, some of the characters for Polish, Turkish, and Czech will be modified.

P031 [Motor NP Volts]

Related Parameter(s):

b004

,

A530

,

A531

,

A532

,

A533

Stop drive before changing this parameter.

Sets the motor nameplate rated volts.

Values

Default:

Drive Rated Volts

Min/Max:

10V (for 230V Drives), 20V (for 460V Drives), 25V (for 600V Drives)/Drive Rated Volts

Display:

1V

P032 [Motor NP Hertz]

Related Parameter(s):

A493

,

A530

,

A531

,

A532

,

A533

Stop drive before changing this parameter.

Sets the motor nameplate rated frequency.

Values

Default:

60 Hz

Min/Max:

15/500 Hz

Display:

1 Hz

P033 [Motor OL Current]

Related Parameter(s):

t069

,

t072

,

t076

,

t081

,

A484

,

A485

,

A493

Sets the motor nameplate overload current. Used to determine motor overload conditions and can be set from 0.1 A to 200% of drive rated current.

Values

Default:

Drive Rated Amps

Min/Max:

0.0/(Drive Rated Amps x 2)

Display:

0.1 A

IMPORTANT

The drive will fault on an F007 “Motor Overload” if the value of this parameter is exceeded by 150% for 60 s.